The E10-Feeder relay is designed specifically for power capacitor bank protection and control; it is a member of the DTIVA product type in the EuroProt+ product family. The DTIVA products are configured to protect, control and supervise elements of the utility and industrial distribution systems, including radial, looped and meshed distribution networks. Because of the modular architecture, the modules are assembled and configured according to the user’s requirements; from that point on, the software determines the functions.
The EuroCAP configuration tool, which is available free of charge, offers a user-friendly and flexible application for protection, control and measurement functions to ensure that the IED-EP+ devices are fully customisable.
General features
Native IEC 61850 IED with Edition 2 compatibility
Scalable hardware to adapt to different applications
84 HP or 42HP wide rack size (height: 3U)
The pre-defined factory configuration can be customized to the user’s specification with the powerful EuroCAP tool
Flexible protection and control functionality to meet special customer requirements
Advanced HMI functionality via color touchscreen and embedded WEB server, extended measuring, control and monitoring functions
User configurable LCD user screens, which can display SLDs (Single Line Diagrams) with switchgear position indication and control as well as measuring values and several types of controllable objects.
Various protection setting groups available
Enhanced breaker monitoring and control
High capacity disturbance recorder (DRE) and event logging:
DRE for up to 32 analogue and 64 digital signal channels.
Event recorder can store more than 10,000 events.
Several mounting methods: Rack; Flush mounting; Semi-flush mounting; Wall mounting; Wall-mounting with terminals; Flush mounting with IP54 rated cover.
Serial communication: DNP3.0; IEC60870-5-101/103; MODBUS, SPA
The EuroProt+ family can handle several communication protocols simultaneously.
Built-in self-monitoring to detect internal hardware or software errors
Different time sources available: NTP server; Minute pulse; Legacy protocol master; IRIG-B000 or IRIG-B12X
Application
The E10-Feeder device has been designed to protect, control and supervise shunt capacitor banks. The IED offers current-based protection functions, which include three-phase time overcurrent and residual time overcurrent protection. The E10-Feeder also offers breaker failure protection.
Apart from the standard current-based protections, the E10-Feeder relay comes with protection functions specifically designed to protect capacitor banks: capacitor overvoltage protection, capacitor unbalance protection. The device is able to handle and protect different bank arrangements, such as ungrounded single star connection, double star (ungrounded) connection, delta-connected banks, “H” configuration, etc.. The E10-Feeder also offers breaker failure protection.
Voltage measurement is optional in the relay, which includes phase and residual overvoltage protection functions.
Scope of application
Protection and monitoring of capacitor banks
Handling of various bank arrangements
Capacitor unbalance protection for blocks inbridge (“H”) connection, double star connection and double delta connection
Calibration feature to compensate the inherent capacitor bank unbalances to prevent maloperation and increase sensitivity
Ambient temperature monitoring
Protection & control functions
The E10-Feeder configuration measures three phase currents, the residual current and, optionally, three phase voltages and the residual voltage. The realized and optional current- and voltage-based protection functions are listed below.
Protection & control functions
IEC
ANSI
*Inst.
Definite time undervoltage protection function
U<, U<<
27
2 op.
19/12/2024
Loss-of-load (undercurrent) protection function
I<
37
1
20/08/2025
Three-phase time overcurrent protection function
I>, I>>
51
2
04/04/2025
Residual overcurrent protection function
Io>, Io>>
51N/51G
2
04/04/2025
Definite time overvoltage protection function
U>, U>>
59
2 op.
19/12/2024
Residual definite time overvoltage protection function
Uo>, Uo>>
59N
2 op.
20/12/2024
Voltage transformer supervision and dead line detection function
60
1 op.
09/07/2019
Current unbalance function (CT Supervision)
60
1
20/12/2024
Capacitor unbalance protection for blocks in bridge connection function
?
51NC
1
31/07/2024
Capacitor unbalance protection for blocks in double star connection function
51NC
1
31/07/2024
Capacitor unbalance protection for blocks in double star connection (Version ”U”) function
59NC
1 op.
31/07/2024
Capacitor unbalance protection for blocks in double delta connection
51NC
1
31/07/2024
Capacitor overvoltage protection function
?
59C
1
31/07/2024
*The INST. column contains the numbers of the pre-configured function blocks in the factory configuration.These numbers may be different in order to meet the user’s requirements.
Documentation
Product Configuration Options
IEC61850 documents
TISSUEs Implementation Conformance Statement (TICS) for the IEC 61850 Edition 2 server interface in Europrot+ product family
18/04/2023
Protocol Implementation eXtra Information for Testing (PIXIT) for the IEC 61850 Edition 2 server interface in Europrot+ product family
18/04/2023
Protocol Implementation Conformance Statement (PICS) for the IEC 61850 Edition 2 server interface in Europrot+ product family
18/04/2023
Model Implementation Conformance Statement (MICS) for the IEC 61850 Edition 2 server interface in DTIVA product
18/04/2023
Protocol Implementation eXtra Information for Testing (PIXIT) for the IEC 61850 Edition 1 server interface in Europrot+ product family
09/07/2019
Protocol Implementation Conformance Statement (PICS) for the IEC 61850 Edition 1 server interface in Eurorot+ product family
09/07/2019
Model Implementation Conformance Statement (MICS) for the IEC 61850 Edition 1 server interface in the Eurorot+ product family
09/07/2019
Type description
Distributed network components protection & control
18/07/2025
Hardware Guides
Hardware description
05/05/2025
Maintenance guide
28/06/2023
Application Guides
Operating Manual and Troubleshooting Guide - system version: 2.8
02/10/2023
Configuration Descriptions
E10-Feeder configuration description
09/07/2019
E10-Feeder_H product configuration options
11/05/2026
Order
Protecta products can be ordered by using an Order Code. This code specifies the hardware and the configuration. Please always refer to a valid Order Code when placing an order. The Order Code page can be opened by clicking the link below.
Protecta provides own‑developed protection, automation & control devices for power generation, transmission, distribution, industrial and renewable energy (microgrid) applications.