magyar | english || Login | registration
Products»EuroProt+»DTIVA»Capacitor bank protection» E10-Feeder Capacitor bank protection
Overview
42HP84HP

The E10-Feeder relay is designed specifically for power capacitor bank protection and control; it is a member of the DTIVA product type in the EuroProt+ product family.
The DTIVA products are configured to protect, control and supervise elements of the utility and industrial distribution systems, including radial, looped and meshed distribution networks. Because of the modular architecture, the modules are assembled and configured according to the user’s requirements; from that point on, the software determines the functions.

The EuroCAP configuration tool, which is available free of charge, offers a user-friendly and flexible application for protection, control and measurement functions to ensure that the IED-EP+ devices are fully customisable.


 

General features

  • Native IEC 61850 IED with Edition 2 compatibility
  • Scalable hardware to adapt to different applications
  • 84 HP or 42HP wide rack size (height: 3U)
  • The pre-defined factory configuration can be customized to the user’s specification with the powerful EuroCAP tool
  • Flexible protection and control functionality to meet special customer requirements
  • Advanced HMI functionality via color touchscreen and embedded WEB server, extended measuring, control and monitoring functions
  • User configurable LCD user screens, which can display SLDs (Single Line Diagrams) with switchgear position indication and control as well as measuring values and several types of controllable objects.
  • Various protection setting groups available
  • Enhanced breaker monitoring and control
  • High capacity disturbance recorder (DRE) and event logging:
    • DRE for up to 32 analogue and 64 digital signal channels.
    • Event recorder can store more than 10,000 events.
  • Several mounting methods: Rack; Flush mounting; Semi-flush mounting; Wall mounting; Wall-mounting with terminals; Flush mounting with IP54 rated cover.
  • Wide range of communication protocols:
    • Ethernet-based communication: IEC61850; IEC60870-5-104; DNP3.0 TCP; Modbus TCP
    • Serial communication: DNP3.0; IEC60870-5-101/103; MODBUS, SPA
  • The EuroProt+ family can handle several communication protocols simultaneously.
  • Built-in self-monitoring to detect internal hardware or software errors
  • Different time sources available: NTP server; Minute pulse; Legacy protocol master; IRIG-B000 or IRIG-B12X
 

 

Application
42HP84HP

The E10-Feeder device has been designed to protect, control and supervise shunt capacitor banks.
The IED offers current-based protection functions, which include three-phase time overcurrent and residual time overcurrent protection.
The E10-Feeder also offers breaker failure protection.

Apart from the standard current-based protections, the E10-Feeder relay comes with protection functions specifically designed to protect capacitor banks: capacitor overvoltage protection, capacitor unbalance protection. The device is able to handle and protect different bank arrangements, such as ungrounded single star connection, double star (ungrounded) connection, delta-connected banks, “H” configuration, etc.. The E10-Feeder also offers breaker failure protection.

Voltage measurement is optional in the relay, which includes phase and residual overvoltage protection functions.

 

Scope of application

  • Protection and monitoring of capacitor banks
  • Handling of various bank arrangements
  • Capacitor unbalance protection for blocks inbridge (“H”) connection, double star connection and double delta connection
  • Calibration feature to compensate the inherent capacitor bank unbalances to prevent maloperation and increase sensitivity
  • Ambient temperature monitoring
Protection & Control functions

The E10-Feeder configuration measures three phase currents, the residual current and, optionally, three phase voltages and the residual voltage. The realized and optional current- and voltage-based protection functions are listed below.

Protection & control functions IEC ANSI *Inst.
Definite time undervoltage protection function U<, U<< 27 2 op.
Loss-of-load (undercurrent) protection function I< 37 1
Three-phase time overcurrent protection function I>, I>> 51 2
Residual overcurrent protection function Io>, Io>> 51N/51G 2
Definite time overvoltage protection function U>, U>> 59 2 op.
Residual definite time overvoltage protection function Uo>, Uo>> 59N 2 op.
Voltage transformer supervision and dead line detection function 60 1 op.
Current unbalance function 60 1
Capacitor unbalance protection for blocks in bridge connection function 51NC 1
Capacitor unbalance protection for blocks in double star connection function 51NC 1
Capacitor unbalance protection for blocks in double star connection (Version ”U”) function 59NC 1 op.
Capacitor unbalance protection for blocks in double delta connection 51NC 1
Capacitor overvoltage protection function 59C 1
*The INST. column contains the numbers of the pre-configured function blocks in the factory configuration.These numbers may be different in order to meet the user’s requirements.
Documentation
IEC61850 documents version Format Date Size
TISSUEs Implementation Conformance Statement (TICS) for the IEC 61850 Edition 2 server interface in Europrot+ product family 1.0 18/04/2023 569.01 KB
Protocol Implementation eXtra Information for Testing (PIXIT) for the IEC 61850 Edition 2 server interface in Europrot+ product family 1.03 18/04/2023 555.52 KB
Protocol Implementation Conformance Statement (PICS) for the IEC 61850 Edition 2 server interface in Europrot+ product family 1.02 18/04/2023 478.52 KB
Model Implementation Conformance Statement (MICS) for the IEC 61850 Edition 2 server interface in DTIVA product 1.0 18/04/2023 391.88 KB
Protocol Implementation eXtra Information for Testing (PIXIT) for the IEC 61850 Edition 1 server interface in Europrot+ product family 1.1 20/03/2017 259.27 KB
Protocol Implementation Conformance Statement (PICS) for the IEC 61850 Edition 1 server interface in Eurorot+ product family 1.1 20/03/2017 261.09 KB
Model Implementation Conformance Statement (MICS) for the IEC 61850 Edition 1 server interface in the Eurorot+ product family 1.0 21/05/2012 864.71 KB
Type description version Format Date Size
Distributed network components protection & control 1.1 21/02/2020 2.25 MB
Hardware Guides version Format Date Size
Hardware description 2.00 10/02/2023 4.24 MB
Maintenance guide 2.1 28/06/2023 770.85 KB
Application Guides version Format Date Size
Operating Manual and Troubleshooting Guide - system version: 2.8 1.5 19/09/2023 2.69 MB
Configuration Descriptions version Format Date Size
E10-Feeder configuration description 1.0 20/02/2014 2.25 MB
E10-Feeder_H product configuration options 5.5 11/03/2024
-
Order
Protecta products can be ordered by using an Order Code. This code specifies the hardware and the configuration.
Please always refer to a valid Order Code when placing an order.
The Order Code page can be opened by clicking the link below.
This website uses cookies. By further use of this site you agree to these cookies being set. Learn more...