Overview

The E9-GEN is a dedicated generator or generator-transformer block protection and control IED; the relay provides complex protection, control and monitoring functions for generator/step-up transformer blocks. It is a member of the DGEN (former product type: DTRV) product type in the EuroProt+ product family. The EuroProt+ family complex protection in respect of hardware and software is a modular device. Because of the modular architecture, the modules are assembled and configured according to the user’s requirements; from that point on, the software determines the functions.

The DGEN (former product type: DTRV) type is especially designed for protection and control applications of power transformers and generators including generator-transformer blocks. Additionally the DGEN (former product type: DTRV) product type includes variety of versatile protection functions to meet the user’s the most demanding requirements.


The EuroCAP configuration tool, which is available free of charge, offers a user-friendly and flexible application for protection, control and measurement functions to ensure that the IED-EP+ devices are fully customisable.

General features

  • Native IEC 61850 IED with Edition 2 compatibility
  • Scalable hardware to adapt to different applications
  • 84 HP or 42HP wide rack size (height: 3U)
  • The pre-defined factory configuration can be customized to the user’s specification with the powerful EuroCAP tool
  • Flexible protection and control functionality to meet special customer requirements
  • Advanced HMI functionality via color touchscreen and embedded WEB server, extended measuring, control and monitoring functions
  • User configurable LCD user screens, which can display SLDs (Single Line Diagrams) with switchgear position indication and control as well as measuring values and several types of controllable objects.
  • Various protection setting groups available
  • Enhanced breaker monitoring and control
  • High capacity disturbance recorder (DRE) and event logging:
    • DRE for up to 32 analogue and 64 digital signal channels.
    • Event recorder can store more than 10,000 events.
  • Several mounting methods: Rack; Flush mounting; Semi-flush mounting; Wall mounting; Wall-mounting with terminals; Flush mounting with IP54 rated cover.
  • Wide range of communication protocols:
    • Ethernet-based communication: IEC61850; IEC60870-5-104; DNP3.0 TCP; Modbus TCP
    • Serial communication: DNP3.0; IEC60870-5-101/103; MODBUS, SPA
  • The EuroProt+ family can handle several communication protocols simultaneously.
  • Built-in self-monitoring to detect internal hardware or software errors
  • Different time sources available: NTP server; Minute pulse; Legacy protocol master; IRIG-B000 or IRIG-B12X

Application

The E9-GEN is designed to be the main protection and control IED for synchronous power generators or entire generator blocks including the step-up transformer. The relay is member of the DGEN (former product type: DTRV) product type in the EuroProt+ product family.

The E9-GEN relay includes variety of versatile protection functions along with the main differential protection, such as overcurrent, over-/undervoltage, frequency protections. The device contains several functions especially made for generator applications as well, e.g. thermal-based negative sequence overcurrent protection, voltage dependent overcurrent, inadvertent energizing protections, loss of excitation, 100% stator earth fault protection, rotor earth fault protection etc. It can be applied as a back-up protection relay for downstream equipment (e.g. feeders, cables etc.).

The E9-GEN generator(block) protection relay can support the double breaker terminals such as breaker and a half, or ring bus topologies. Synchro-check is also available.

The IED includes wide range of control and supervisory functions which provide full control and user defined interlocking schemes for the primary switchgear at the substation.

THE SCOPE OF APPLICATION

  • Generator differential protection or block differential protection with two ends
  • In case of block differential protection:
    • Automatic phase shift and turns ratio compensation of the step-up transformer
    • 2nd and 5th harmonics restraint for transformer inrush and overexcitation detection
  • Protections specifically made for generator applications
    • Voltage dependent overcurrent protections
    • Interturn fault protection for larger generators (current or voltage based, depending on the winding)
    • Loss of excitation protection
    • Pole slipping (out-of-step) protection
    • Rotor earth fault protection for isolated/ungrounded or middle-grounded rotors
  • Different kinds of 95% earth fault protections:
    • Residual overcurrent (can be sensitive depending on the CT)
    • Residual overvoltage
    • Restricted earth fault
  • 100% Stator earth fault protections:
    • 3rd harmonic undervoltage
    • 3rd harmonic differential overvoltage by measuring the residual voltage in the neutral and the terminal point (two operation modes if generator CB is present)
  • Restricted earth-fault protection
  • The implemented protection functions provide back-up protection for downstream equipment (e.g. feeders, cables etc.).
  • Independent trip logic and circuit supervision for each trip circuit (circuit breaker, excitation, turbine valve etc.)
  • Support for the double breaker terminals such as breaker and a half, or ring bus topologies
  • Supervision of current and voltage transformers
  • Programmable interlocking schemes
  • Optional external unit:
    • Remote I/O unit (RIO)
  • Optional transducer I/Os (RTD/mA)

Protection & control functions

The E9-GEN configuration measures three phase currents from both sides of the generator (or the neutral side of the generator and the HV side of the step-up transformer), the residual current(s), three phase voltages of the generator, residual voltage(s). The main protection functions are the generator (block) differential protection, overcurrent, voltage dependent overcurrent, frequency, loss of excitation and earth-fault protection functions. The additional protection functions are available to provide the necessary complexity according to the generator´s protection needs as well as back-up protections for downstream equipment (e.g. feeders, cables etc.). 

Protection & control functions IEC ANSI *Inst.
Directional Element function (2.10 systems only) ? ? 1 11/07/2025
Differential Protection Function (versions 5 and up on 2.10 systems) 3IdT > 87T 1 op. 18/12/2024
Impedance protection with compounded circular characteristic function Z< 21 1 30/07/2024
Overexcitation protection function V/Hz 24 1 20/12/2024
Synchro check synchro switch function SYNC 25 1 op. 14/11/2024
Definite time undervoltage protection function U<, U<< 27 2 19/12/2024
Third harmonic undervoltage protection function U3h< 64/27TN 1 op. 09/07/2019
Directional residual wattmetric earth-fault protection function Po> 32N 1 14/10/2024
Directional overpower protection function P> 32 2 20/12/2024
Directional underpower protection function P< 37 1 20/12/2024
GGIORTD temperature measurement function 38/49T 4 op. 27/11/2024
Loss of excitation protection function (Version 40Q) X< 40Q 2 27/12/2024
Loss of excitation protection function (Version 40Z) Z< 40Z 2 op. 09/07/2019
Negative sequence overcurrent protection function I2> 46 1 04/04/2025
Negative sequence overcurrent protection for generators function I2> 46G 1 23/09/2026
Negative sequence definite time overvoltage protection function U2 > 47 1 10/10/2024
Line thermal protection function T > 49 1 03/01/2025
Breaker failure protection functions CBFP 50BF 1 03/10/2022
Three-phase instantaneous overcurrent protection function I >>> 50 2 17/01/2025
Residual instantaneous overcurrent protection function Io>>> 50N/50G 2 09/12/2025
Generator inadvertent energizing protection function I>>> U< 50V/27AE 1 09/07/2019
Three-phase time overcurrent protection function I>, I>> 51 2 04/04/2025
Residual overcurrent protection function Io>, Io>> 51N/51G 2 04/04/2025
Interturn fault protection function (split phase/current based) Ii> 50SP 1 op. 09/07/2019
Voltage dependent overcurrent protection function I> U< 51V 1 10/08/2021
Definite time overvoltage protection function U>, U>> 59 2 19/12/2024
Residual definite time overvoltage protection function Uo>, Uo>> 59N 2 20/12/2024
Residual start-up overvoltage protection function UNs> 59NS 1 21/07/2023
Interturn fault protection function (voltage based) Ui> 59I 1 op. 11/12/2020
Third harmonic differential overvoltage protection function U3hd> 59TD/64TN 1 op. 09/07/2019
Voltage transformer supervision and dead line detection function 60 1 09/07/2019
Current unbalance function (CT Supervision) 60 2 20/12/2024
Rotor earth fault function and hardware description for isolated rotors 64R 1 op. 11/12/2020
Rotor earth fault function and hardware description for middle-grounded rotors 64R 1 op. 11/12/2020
Directional three-phase overcurrent protection function I Dir>, I Dir>> 67 2 04/04/2025
Directional residual time overcurrent protection function Io Dir>, Io Dir>> 67N/67G 2 03/12/2025
Inrush current detection function I2h> 68 1 20/12/2024
Pole slipping protection function ΔZ/Δt 78 1 08/03/2022
Overfrequency protection function f>, f>> 81O 2 20/12/2024
Underfrequency protection function f<, f<< 81U 2 20/12/2024
Rate of change of frequency function df/dt 81R 2 20/12/2024
Generator differential protection function 3IdG > 87G/87M 1 09/07/2019
Restricted earth-fault protection function REF 87N 2 op. 10/12/2024
*The INST. column contains the numbers of the pre-configured function blocks in the factory configuration.These numbers may be different in order to meet the user’s requirements.

Documentation

Product Configuration Options
Hardware Guides
Hardware description 31/07/2026
Maintenance guide 28/06/2023
Application Guides
Operating Manual and Troubleshooting Guide - system version: 2.8 02/10/2023
IEC61850 documents
TISSUEs Implementation Conformance Statement (TICS) for the IEC 61850 Edition 2 server interface in Europrot+ product family 18/04/2023
Protocol Implementation eXtra Information for Testing (PIXIT) for the IEC 61850 Edition 2 server interface in Europrot+ product family 18/04/2023
Protocol Implementation Conformance Statement (PICS) for the IEC 61850 Edition 2 server interface in Europrot+ product family 18/04/2023
Model Implementation Conformance Statement (MICS) for the IEC 61850 Edition 2 server interface in DGEN product 18/04/2023
Protocol Implementation eXtra Information for Testing (PIXIT) for the IEC 61850 Edition 1 server interface in Europrot+ product family 09/07/2019
Protocol Implementation Conformance Statement (PICS) for the IEC 61850 Edition 1 server interface in Eurorot+ product family 09/07/2019
Model Implementation Conformance Statement (MICS) for the IEC 61850 Edition 1 server interface in the Eurorot+ product family 09/07/2019
Protection function testing (XRIO files)
Transformer and line differential protection (ANSI:87T, 87L; IEC:3IdT, 3IdL) 06/07/2020
Configuration Descriptions
E9-TR configuration description 09/07/2019