The E5-TR is a dedicated three-winding transformer protection and control IED; the relay provides complex protection, control and monitoring functions for three-winding power transformers. It is member of the DTRV product type in the EuroProt+ product family.
The DTRV type is designed particularly for protection and control applications of power transformers and generators including generator-transformer blocks. Additionally, the DTRV product type includes a variety of versatile protection functions to meet the users´ most exacting requirements.
Because of the implemented control, measuring and monitoring function, the IED can also be used as a bay control unit.
The EuroCAP configuration tool, which is available free of charge, offers a user-friendly and flexible application for protection, control and measurement functions to ensure that the IED-EP+ devices are fully customisable.
General features
Native IEC 61850 IED with Edition 2 compatibility
Scalable hardware to adapt to different applications
84 HP or 42HP wide rack size (height: 3U)
The pre-defined factory configuration can be customized to the user’s specification with the powerful EuroCAP tool
Flexible protection and control functionality to meet special customer requirements
Advanced HMI functionality via color touchscreen and embedded WEB server, extended measuring, control and monitoring functions
User configurable LCD user screens, which can display SLDs (Single Line Diagrams) with switchgear position indication and control as well as measuring values and several types of controllable objects.
Various protection setting groups available
Enhanced breaker monitoring and control
High capacity disturbance recorder (DRE) and event logging:
DRE for up to 32 analogue and 64 digital signal channels.
Event recorder can store more than 10,000 events.
Several mounting methods: Rack; Flush mounting; Semi-flush mounting; Wall mounting; Wall-mounting with terminals; Flush mounting with IP54 rated cover.
Serial communication: DNP3.0; IEC60870-5-101/103; MODBUS, SPA
The EuroProt+ family can handle several communication protocols simultaneously.
Built-in self-monitoring to detect internal hardware or software errors
Different time sources available: NTP server; Minute pulse; Legacy protocol master; IRIG-B000 or IRIG-B12X
Application
The E5-TR is a dedicated three-winding transformer protection and control IED; the relay provides complex protection, control and monitoring functions for three-winding power transformers. It is member of the DTRV product type in the EuroProt+ product family.
The E5-TR relay provides a variety of versatile protection functions along with the main transformer differential protection, such as 3ph, Io and I2 overcurrent protection, overload protection, restricted earth-fault protection etc.
Sensitive restricted earth-fault protection (REF) is the final element in the overall differential protection system, which detects even single phase-to-ground faults close to the grounded neutral of the transformer.
The multiple instances of the implemented three-phase and residual overcurrent functions are provided for the segregated protection of both transformer windings.
Furthermore, several voltage-based protection functions are available for one transformer winding based on the three-phase voltage measurement. The connections of the voltage measurement depends on the current application.
The E5-TR transformer protection relay can support double-breaker terminals on any side of the transformer such as breaker and a half or ring bus topology. Automatic phase shift and turns ratio compensation for all types of transformer winding connections.
It can be used as a back-up protection relay for downstream equipment (e.g. feeders, cables).
The IED includes a wide range of control and supervisory functions, which provide full control and user-defined interlocking schemes for the primary switchgear at the substation.
scope of application
3-winding transformer protection and control device with main transformer differential protection and several additional protection functions;
The versatile protections functions can provide back-up protection relay for downstream equipment (e.g. feeders, cables etc.),
Protection for all kinds of power transformers (including auto-transformers),
1-/3-phase tripping and support for double breaker terminals such as breaker and a half or ring bus topologies
Three-phase transformer differential protection:
Automatic phase shift and turns ratio compensation of the transformer,
2nd and 5th harmonics restraint for transformer inrush and overexcitation detection,
Residual current elimination feature is available if there is a neutral grounding transformer in the protected zone on the secondary side of the transformer,
Sensitive restricted earth-fault protection,
Several voltage-based protection functions are available through the three-phase voltage measurement,
Current unbalance detection of Current Transformers,
Programmable interlocking schemes,
Optional external units:
28 input/ 5 output tap changer transcoder (TRCS),
Remote I/O unit (RIO),
Optional transducer I/Os (RTD/mA),
Optional impedance protection
Protection & control functions
The E5-TR configuration measures three phase currents, the residual current component from both sides of a three-winding, three-phase transformer and, additionally, three phase voltages. These measurements allow, in addition to the current- and voltage-based functions, directionality extension of the residual overcurrent function.
The main protection functions are the transformer differential protection and the restricted earth-fault protection functions. Based on the voltage measurement, the frequency is also evaluated to facilitate frequency-based protection functions.
The additional protection functions can provide back-up protection relay for downstream equipment (e.g. feeders, cables etc.).
Protection & control functions
IEC
ANSI
*Inst.
Differential Protection Function (versions 5 and up on 2.10 systems)
3IdT >
87T
1
18/12/2024
Overexcitation protection function
V/Hz
24
1
20/12/2024
Definite time undervoltage protection function
U<, U<<
27
2
19/12/2024
Negative sequence overcurrent protection function
I2>
46
1
04/04/2025
Negative sequence definite time overvoltage protection function
U2 >
47
1
10/10/2024
Line thermal protection function
T >
49
1
03/01/2025
Three-phase instantaneous overcurrent protection function
I >>>
50
3
17/01/2025
Residual instantaneous overcurrent protection function
Io>>>
50N/50G
3
09/12/2025
Breaker failure protection functions
CBFP
50BF
3
03/10/2022
Three-phase time overcurrent protection function
I>, I>>
51
3
04/04/2025
Residual overcurrent protection function
Io>, Io>>
51N/51G
3
04/04/2025
Definite time overvoltage protection function
U>, U>>
59
2
19/12/2024
Residual definite time overvoltage protection function
Uo>, Uo>>
59N
2
20/12/2024
Current unbalance function (CT Supervision)
60
3
20/12/2024
Directional residual time overcurrent protection function
Io Dir>, Io Dir>>
67N/67G
2
03/12/2025
Overfrequency protection function
f>, f>>
81O
2
20/12/2024
Underfrequency protection function
f<, f<<
81U
2
20/12/2024
Rate of change of frequency function
df/dt
81R
2
20/12/2024
Restricted earth-fault protection function
REF
87N
3
10/12/2024
*The INST. column contains the numbers of the pre-configured function blocks in the factory configuration.These numbers may be different in order to meet the user’s requirements.
Documentation
Product Configuration Options
IEC61850 documents
TISSUEs Implementation Conformance Statement (TICS) for the IEC 61850 Edition 2 server interface in Europrot+ product family
18/04/2023
Protocol Implementation eXtra Information for Testing (PIXIT) for the IEC 61850 Edition 2 server interface in Europrot+ product family
18/04/2023
Protocol Implementation Conformance Statement (PICS) for the IEC 61850 Edition 2 server interface in Europrot+ product family
18/04/2023
Model Implementation Conformance Statement (MICS) for the IEC 61850 Edition 2 server interface in DTRV product
18/04/2023
Protocol Implementation eXtra Information for Testing (PIXIT) for the IEC 61850 Edition 1 server interface in Europrot+ product family
09/07/2019
Protocol Implementation Conformance Statement (PICS) for the IEC 61850 Edition 1 server interface in Eurorot+ product family
09/07/2019
Model Implementation Conformance Statement (MICS) for the IEC 61850 Edition 1 server interface in the Eurorot+ product family
09/07/2019
Type description
Transformer protection & control
18/07/2025
Hardware Guides
Hardware description
31/07/2026
Maintenance guide
28/06/2023
Application Guides
Operating Manual and Troubleshooting Guide - system version: 2.8
02/10/2023
Configuration Descriptions
E5-TR configuration description
09/07/2019
E5-TR_H product configuration options
05/08/2026
E5-TR_F product configuration options
05/08/2026
Order
Protecta products can be ordered by using an Order Code. This code specifies the hardware and the configuration. Please always refer to a valid Order Code when placing an order. The Order Code page can be opened by clicking the link below.
Protecta provides own‑developed protection, automation & control devices for power generation, transmission, distribution, industrial and renewable energy (microgrid) applications.