Products»EuroProt+»DTRV» E1-TR Two-winding transformer differential protection and control device
Overview
84HP wide84HP wide back42HP

The E1-TR is a dedicated two-winding transformer protection and control IED; the relay provides complex protection, control and monitoring functions for two-winding power transformers. This device is a member of the DTRV product type in the EuroProt+ product family. The EuroProt+ family complex protection - in respect of hardware and software - is a modular device. Because of the modular architecture, the modules are assembled and configured according to the user’s requirements; from that point on, the software determines the functions.

The DTRV type is designed particularly for protection and control applications of power transformers and generators including generator-transformer blocks. Additionally, the DTRV product type includes a variety of versatile protection functions to meet the users´ most exacting requirements.

Because of the implemented control, measuring and monitoring function, the IED can also be used as a bay control unit.

The EuroCAP configuration tool, which is available free of charge, offers a user-friendly and flexible application for protection, control and measurement functions to ensure that the IED-EP+ devices are fully customisable.

General features

  • Native IEC 61850 IED with Edition 2 compatibility
  • Scalable hardware to adapt to different applications
  • 84 HP or 42HP wide rack size (height: 3U)
  • The pre-defined factory configuration can be customized to the user’s specification with the powerful EuroCAP tool
  • Flexible protection and control functionality to meet special customer requirements
  • Advanced HMI functionality via color touchscreen and embedded WEB server, extended measuring, control and monitoring functions
  • User configurable LCD user screens, which can display SLDs (Single Line Diagrams) with switchgear position indication and control as well as measuring values and several types of controllable objects.
  • Various protection setting groups available
  • Enhanced breaker monitoring and control
  • High capacity disturbance recorder (DRE) and event logging (data is stored in non-volatile memory):
    • DRE for up to 32 analogue and 64 digital signal channels.
    • Event recorder can store more than 10,000 events.
  • Several mounting methods: Rack; Flush mounting; Semi-flush mounting; Wall mounting; Wall-mounting with terminals; Flush mounting with IP54 rated cover.
  • Wide range of communication protocols:
    • Ethernet-based communication: IEC61850; IEC60870-5-104; DNP3.0 TCP; Modbus TCP
    • Serial communication: DNP3.0; IEC60870-5-101/103; MODBUS, SPA
  • The EuroProt+ family can handle several communication protocols simultaneously.
  • Built-in self-monitoring to detect internal hardware or software errors
  • Different time sources available: NTP server; Minute pulse; Legacy protocol master; IRIG-B000 or IRIG-B12X
Application
84HP wide84HP wide back42HP

The E1-TR is designed to be the main protection and control IED for two-winding power transformers, including auto-transformers. The relay is a member of the DTRV product type in the EuroProt+ product family.

The E1-TR relay provides a variety of versatile protection functions along with the main transformer differential protection, such as 3ph, Io and I2 overcurrent protection, thermal overload protection, restricted earth fault protection (low- or high-impedance option) etc. It can be used as a back-up protection relay for downstream equipment (e.g. feeders, cables).

The E1-TR transformer protection relay can support double-breaker terminals on any side of the transformer such as breaker and a half or ring bus topology.

The IED includes a wide range of control and supervisory functions, which provide full control and user-defined interlocking schemes for the primary switchgear at the substation.

 


scope of application

  • 2-winding transformer protection and control device with main transformer differential protection and several additional protection functions
  • The implemented protection functions provide back-up protection for downstream equipment (e.g. feeders, cables etc.).
  • Protection for all kinds of power transformers (including auto-transformers)
  • 1-/3-phase tripping and support for double breaker terminals such as breaker and a half  or ring bus topologies
  • Three-phase transformer differential protection:
    • Automatic phase shift and turns ratio compensation of the transformer.
    • 2nd and 5th harmonics restraint for transformer inrush and overexcitation detection
  • Restricted earth-fault protection
  • Current unbalance detection of CT
  • Programmable interlocking schemes
  • Optional external units:
    • 28 input/ 5 output tap changer transcoder (TRCS)
    • Remote I/O unit (RIO)
  • Optional transducer I/Os (RTD/mA)
  • Optional impedance protection

 

Protection & Control functions

The E1-TR configuration measures three phase currents and the zero sequence current of both sides of a two-winding, three-phase transformer. The main protection functions are transformer differential protection and restricted earth-fault protection functions. The additional protection functions can provide back-up protection for downstream equipment (e.g. feeders, cables).

Protection & control functions IEC ANSI *Inst.
Negative sequence overcurrent protection function I2> 46 1
Line thermal protection function T > 49 1
Three-phase instantaneous overcurrent protection function I >>> 50 2
Residual instantaneous overcurrent protection function Io>>> 50N/50G 2
Breaker failure protection functions CBFP 50BF 2
Three-phase time overcurrent protection function I>, I>> 51 2
Residual overcurrent protection function Io>, Io>> 51N/51G 2
Current unbalance function 60 2
Restricted earth-fault protection function REF 87N 2
Differential protection function 3IdT > 87T 1
*The INST. column contains the numbers of the pre-configured function blocks in the factory configuration.These numbers may be different in order to meet the user’s requirements.
Documentation
Type description version Format Date Size
Transformer protection & control 1.0 05/04/2019 2.08 MB
Hardware Guides version Format Date Size
Hardware description 2.00 10/02/2023
4.24 MB
Maintenance guide 2.0 18/11/2022 769.82 KB
Application Guides version Format Date Size
Operating Manual and Troubleshooting Guide FW version 2.8 1.4 14/03/2023
3.59 MB
IEC61850 documents version Format Date Size
Model Implementation Conformance Statement - MICS 1.0 21/05/2012 864.71 KB
Protocol Implementation Conformance Statement - PICS 1.1 20/03/2017 261.09 KB
Protocol Implementation Extra Information - PIXIT 1.1 20/03/2017 259.27 KB
Configuration Descriptions version Format Date Size
E1-TR configuration description 1.0 24/03/2014 3.00 MB
E1-TR_H product configuration options 4.2 22/11/2022 -
E1-TR_F product configuration options 4.2 13/01/2023 -
Order
Protecta products can be ordered by using an Order Code. This code specifies the hardware and the configuration.
Please always refer to a valid Order Code when placing an order.
The Order Code page can be opened by clicking the link below.
E1-TR_H: 42hp_35_rj_on_order_tr_2w.jpg E1-TR_F: 84hp_35_rj_on_order_tr_2w.jpg