Variant 2

Dir. 3Ph+Io overcurrent, small generator protection & autorecloser

Variant 2

Dir. 3Ph+Io overcurrent, small generator protection & autorecloser

Variant 2

Dir. 3Ph+Io overcurrent, small generator protection & autorecloser

Variant 2

Dir. 3Ph+Io overcurrent, small generator protection & autorecloser

Overview

Similarly to Variant 1, Variant 2 can be used as the main or backup protection of overhead lines and cable networks. Because of its voltage- and frequency-based functions, Variant 2 is recommended especially for applications where small generators are connected to the network / smart grids.

It is a member of the S24 series, which is part of the EuroProt+ Smart Line. Members of the Smart Line also offer a wide range of functions but they do so in a small, compact enclosure so that they can be installed in locations with limited space available for the protection equipment.

The S24 series contain special selections of the EuroProt+ modules and functions, composed with cost effectiveness in mind. Depending on the standard configuration chosen (Variant 1, Variant 2,…), the IED is adapted to the protection of medium-voltage feeders in isolated neutral, resistance earthed, compensated and solidly earthed networks. Once the application-specific settings have been defined for the standard configuration IED, it can be put into service directly. Areas of application include protection functions for a large variety of applications, e.g. transformer differential and restricted earth fault protection, frequency and voltage based protection, motor protection, thermal overload protection.

The EuroCAP configuration tool, which is available free of charge, offers a user-friendly and flexible application for protection, control and measurement functions to ensure that the IED-EP+ S24 devices are fully customizable.

General features

  • Native IEC 61850 IED with Edition 2 compatibility
  • Standard module layouts with options
  • 24 HP wide rack size (height: 3U)
  • The pre-defined factory configuration can be customized to the user’s specification with the powerful EuroCAP tool
  • Different HMI types: advanced HMI with color touchscreen and black-and-white display with 4 tactile push buttons. An embedded web server and extended measuring, control and monitoring functions are also available for both types
  • User configurable LCD user screens for the HMI-type color touchscreen, which can display SLDs (Single Line Diagrams) with switchgear position indication and control as well as measuring values and several types of controllable objects
  • Various protection setting groups
  • Enhanced breaker monitoring and control
  • High capacity disturbance recorder (DRE) and event logging:
    • DRE for up to 32 analogue and 64 digital signal channels
    • Event recorder can store more than 10,000 events
  • Mounting methods: Flush mounting; Semi-flush mounting; Din rail mounting
  • Wide range of communication protocols:
    • Ethernet-based communication: IEC61850; IEC60870-5-104; DNP3.0 TCP; Modbus TCP
    • Serial communication: DNP3.0; IEC60870-5-101/103; MODBUS, SPA
    • Legacy network based protocols via 100Base-FX and 10/100Base-TX (RJ45)
  • Optional communication ports: Fiber optical Ethernet (MM/ST, SM/FC), RJ45, Serial POF, Serial glass fiber, RS-485/422
  • Handling of several communication protocols simultaneously
  • Built-in self-monitoring to detect internal hardware or software errors
  • Different time sources available: NTP server; Minute pulse; Legacy protocol master



Application

Variant 2 can be used as the main or backup protection of overhead lines and cable networks. The voltage- and frequency-based functions facilitate the application of the IED for the protection and control of small generators as well. The relay is member of the S24 product type in the EuroProt+ product family.

The Variant 2 relay includes a variety of versatile feeder protection functions based on both current and voltage measurement, such as three-phase, residual and negative sequence overcurrent protection, undercurrent protection, thermal overload protection and directional three-phase and residual overcurrent protection. The voltage- and frequency-based functions can serve as the main protection of small generators. Voltage-dependent overcurrent, vector jump, over- and undervoltage functions as well as over- and underfrequency, frequency change protection, etc. are also available. It can be used as a back-up protection relay for downstream equipment (e.g. feeders, cables). The automatic reclosing function is also part of the standard configuration.

The IED includes a wide range of control and supervisory functions, which provide full control and user-defined interlocking schemes for the primary switchgear at the substation.



SCOPE OF APPLICATION

  •      Three-phase and residual overcurrent and directional overcurrent, thermal overload protection functions for overhead lines and cable networks
  •      Over- and undervoltage protection functions
  •      Additional protection and control functions especially for small generators: negative sequence overcurrent, voltage dependent overcurrent, vector jump, frequency-based protection, overexcitation detection
  •      The implemented protection functions provide back-up protection for downstream equipment (e.g. feeders, cables etc.)
  •      Optional restricted earth fault protection function for the simple protection of small transformers
  •      Automatic reclosing function
  •      Breaker failure protection function
  •      Current unbalance detection of CT’s
  •      VT supervision function
  •      Programmable interlocking schemes

 

Protection & control functions

The Variant 2 configuration measures the three-phase currents, the residual current component as well as three-phase voltages. These measurements add directionality extension to the configured phase and residual overcurrent functions t  o the current- and voltage-based functions. The frequency is also evaluated (based on the voltage measurement) to realize frequency-based protection functions. It is intended to protect overhead line or cable networks and small generators. The scope of functions is supplemented with the automatic reclosing function. The configuration is designed to meet the requirements of a medium-voltage field unit.

The restricted earth fault protection function is available as an option for small transformer protection.

Protection & control functions IEC ANSI *Inst.
Directional Element function (2.10 systems only) ? ? 1 11/07/2025
Overexcitation protection function V/Hz 24 1 20/12/2024
Definite time undervoltage protection function U<, U<< 27 2 19/12/2024
Directional overpower protection function P> 32 1 20/12/2024
Directional underpower protection function P< 37 1 20/12/2024
Negative sequence overcurrent protection function I2> 46 1 04/04/2025
Broken conductor protection I2/I1> 46BC 1 30/06/2020
Negative sequence overcurrent protection for generators function I2> 46G 1 23/09/2026
Negative sequence definite time overvoltage protection function U2 > 47 1 10/10/2024
Line thermal protection function T > 49 1 03/01/2025
Three-phase instantaneous overcurrent protection function I >>> 50 1 17/01/2025
Residual instantaneous overcurrent protection function Io>>> 50N/50G 1 09/12/2025
Breaker failure protection functions CBFP 50BF 1 03/10/2022
Three-phase time overcurrent protection function I>, I>> 51 2 04/04/2025
Residual overcurrent protection function Io>, Io>> 51N/51G 2 04/04/2025
Voltage dependent overcurrent protection function I> U< 51V 1 10/08/2021
Definite time overvoltage protection function U>, U>> 59 2 19/12/2024
Residual definite time overvoltage protection function Uo>, Uo>> 59N 2 20/12/2024
Voltage transformer supervision and dead line detection function 60 1 09/07/2019
Current unbalance function (CT Supervision) 60 1 20/12/2024
Directional three-phase overcurrent protection function I Dir>, I Dir>> 67 2 04/04/2025
Directional residual time overcurrent protection function Io Dir>, Io Dir>> 67N/67G 2 03/12/2025
Inrush current detection function I2h> 68 1 20/12/2024
Automatic reclosing function for medium voltage networks 0 -> 1 79 1 10/12/2024
Overfrequency protection function f>, f>> 81O 2 20/12/2024
Underfrequency protection function f<, f<< 81U 2 20/12/2024
Rate of change of frequency function df/dt 81R 2 20/12/2024
Vector jump protection function ΔφU> 78VJ 1 09/07/2019
Restricted earth-fault protection function REF 87N op. 10/12/2024
*The INST. column contains the numbers of the pre-configured function blocks in the factory configuration.These numbers may be different in order to meet the user’s requirements.

Documentation

Product Configuration Options
Brochures
EuroProt+ overview 19/02/2021
System Description
IED-EP+ S24 general specification 19/02/2021
Hardware Guides
Maintenance guide 28/06/2023
Hardware description 31/07/2026
IEC61850 documents
TISSUEs Implementation Conformance Statement (TICS) for the IEC 61850 Edition 2 server interface in Europrot+ product family 18/04/2023
Protocol Implementation eXtra Information for Testing (PIXIT) for the IEC 61850 Edition 2 server interface in Europrot+ product family 18/04/2023
Protocol Implementation Conformance Statement (PICS) for the IEC 61850 Edition 2 server interface in Europrot+ product family 18/04/2023
Protocol Implementation eXtra Information for Testing (PIXIT) for the IEC 61850 Edition 1 server interface in Europrot+ product family 09/07/2019
Protocol Implementation Conformance Statement (PICS) for the IEC 61850 Edition 1 server interface in Eurorot+ product family 09/07/2019
Model Implementation Conformance Statement (MICS) for the IEC 61850 Edition 1 server interface in the Eurorot+ product family 09/07/2019
Configuration Descriptions
Variant 2 configuration description 30/05/2023
Variant 2 product configuration options 27/07/2026